Welcome to the Australia Website

We have detected that you may prefer the Global site. Please use the language dropdown above to change your selection if required.

Go to Global

The ISO5167V application module is implemented against the ISO 5167-1:1991(E) Standard and provides the following functionality:

  • Calculation and display of the mass and volume flowrates through Venturi tubes
  • Calculation and display of the Reynolds number
  • Four different tapping types
  • Calculations for gas or liquid
  • Standard supervisory workstation interface
  • Standard software block
  • Status and alarm display
  • Engineer point display
  • External conditions can be used to generate additional alarms

The ISO5167V application module forms part of a library of software function blocks designed to aid the implementation of flow calculation for Venturi tubes. The calculation is based on SI units (barG, °C and kg/hr)

Applications

The application module offers the functionality required to calculate mass and volume flowrates of fluids through Venturi tubes with either of the following tappings:

  • As Cast
  • Machined
  • Rough Weld
  • Nozzle

The module processes calibration and lab data and offers intermediate values such as corrected throat and pipe diameters.

Outline Specification

I/O

  • Differential Pressure input
  • Upstream Static Line Pressure input
  • Upstream Line Temperature input
  • Upstream Density input
  • Operator/Calibration Parameters
  • Venturi Tube Calibration Diameter and Temperature
  • Venturi Tube Expansion Factor
  • Pipe Calibration Diameter and Temperature
  • Pipe Expansion Factor
  • Isentropic Exponent
  • Dynamic Viscosity
  • Relative Density
  • Specific Heat Ratio

Alarms

  • Diameter Ratio out of Range (Beta)
  • Reynolds Number out of Range

Calculations

  • Mass Flowrate
  • Standard Volumetric Flowrate
  • Corrected Venturi tube and Pipe Diameters
  • Pressure Ratio
  • Diameter Ratio
  • Expansibility Factor
  • Discharge Coefficient
  • Reynolds Number
  • Downstream Static Line Pressure
  • Upstream Line Temperature

Product Selector

Package icon
Need help choosing the right product?

Our tool will match the best product to your needs

Launch product selector

Contact Us

close
close